Jablotron

LD-12 Flood detector

The detector is a water flood indicator for rooms (e.g. cellars, bathrooms). This information is sent to an alarm system for alert message transmission.The LD-12 detector can be connected to the input terminals of alarm systems.

Flood detector

LD-12 Flood detector

The red wire is connected to +12V and the black wire to GND. During use, if electrodes are connected by water (e.g. by a water flood), the blue wire is connected to GND and the yellow wire is disconnected from GND. If the connection stops (no water), the blue wire is disconnected from GND and the yellow wire connect to GND.

Especificações técnicas

Operating environment II. internal
Operational temperature range -10 to +40 °C
Output 200 mA max.
Power supply 12 V DC ± 15% ; 2 mA
Alarm condition water flood
Complies with EN 50130-4, EN 55022

Produtos relacionados

EI208DW Detetor autónomo de gás CO com display

Serve para detetar o gás CO (monóxido de carbono) e advertir a tempo dos seus efeitos perigosos para a saúde humana. O detetor está certifi cado para a instalação em interiores de edifícios, trailers e embarcações. Os detetores indicam acusticamente uma concentração perigosa do monóxido de carbono (CO), assim como opticamente, pela lâmpada sinalizadora. Na versão EI 208DW a indicação também é feita mediante a visualização no display.

EI208W Detetor autónomo de gás CO

Serve para detetar o gás CO (monóxido de carbono) e advertir a tempo dos seus efeitos perigosos para a saúde humana. O detetor está certifi cado para a instalação em interiores de edifícios, trailers e embarcações. Os detetores indicam acusticamente uma concentração perigosa do monóxido de carbono (CO), assim como opticamente, pela lâmpada sinalizadora.

GS-133 Gas Detector - 12 V DC

The GS-133 detector is used to indicate leaking of explosive gases (natural gas, methan, propane, butane). The detector detects two levels of gas concen-tration - different output reactions.

GS-208-CO Wired module for connection of the Ei208W(D) CO detector

This is a plug-in module designed for direct integration in the Ei208W or Ei208DW stand-alone CO detector that will enable its wired connection to a security or another system.

LD-81 Flood detector

The detector indicates room water floods (e.g. cellars, bathrooms). This information is sent to an alarm system for alert message transmission. It is connectible to an Oasis alarm system via a JA-81M wireless detector.

SD-283ST Wired combined smoke and heat detector with built in siren

Detector is used to detect fire hazards in the interior of residential or commercial buildings. The detector is also suitable for installing in caravan trailers or mobile homes. The product is not designed to be installed in industrial premises.

SD-503ST Stand-alone combined smoke and heat detector

The SD-503ST is used to detect fire hazards in the interior of residential or commercial buildings. The detector can be installed in mobile homes or caravans. The product is not designed to be installed in industrial premises.